Voltage drop is the voltage you lose between the point of supply and the far end of the cable. Push 32 A through 50 m of 2.5 mm² and by the time you reach the load, a meaningful chunk of your 230 V is gone — often enough to push you out of compliance and make the gear on the end misbehave.
It's not a safety check like RCDs or earthing — it's a performance and compliance check. Fail it and gear runs hot, motors stall, LEDs flicker, and EV chargers throttle themselves down.
AS/NZS 3000:2018 sets a single total voltage drop limit for low voltage installations: the drop between the point of supply and any point in the installation must not exceed 5% of the nominal voltage at the point of supply. That's it. One number, and it applies to every circuit type — power, cooking, lighting, whatever.
At 230 V single-phase that works out to:
Two quick exceptions to keep in the back pocket:
You'll see it everywhere — trade texts, training material, equipment brochures, even the disclaimer on this page's calculator. It's a sensible design rule of thumb to keep lamp colour and output stable on long runs, and the calculator flags it as a secondary check. But it is not a limit imposed by AS/NZS 3000 or AS/NZS 3008.1 in New Zealand. The only regulatory number is 5%. If you're designing for a client who cares about lighting performance, aim for 3% because it's good practice — not because the standard requires it.
The simplified method from AS/NZS 3008.1.2 Section 4 uses the mV/A.m value for your cable — the voltage drop you'd get per amp per metre of circuit length:
Vd (volts) = (L × I × Vc) ÷ 1000
Where:
For three-phase the formula uses phase-to-phase voltage (400 V in NZ) as the reference, and single-phase values are related to three-phase values by a 1.155 multiplier where the tables are three-phase-based. The calculator above handles both cases.
A 32 A single-phase EV charger, 40 m from the switchboard, 6 mm² multicore copper (default installation method, 75°C operating temperature). Using the standard reference value of 7.3 mV/A.m for 6 mm² under these conditions:
Drop one size to 4 mm² (Vc ≈ 11 under the same conditions) and the drop climbs to around 14.1 V / 6.1% — fails 5%. That's the textbook case where the calculator pushes you up a cable size, and why 6 mm² is the NZ de facto minimum for 32 A continuous loads on anything but the shortest runs.
5% of the nominal voltage at the point of supply, measured to any point in the installation. Set by Clause 3.6.2 of AS/NZS 3000:2018. The 5% is the total across consumer mains, submains and the final sub-circuit combined.
No. AS/NZS 3000:2018 does not impose a 3% lighting limit — the 5% total applies to every circuit. The 3% figure is a common design target for lighting to avoid visible flicker and colour shift, but it's a rule of thumb, not a regulatory cap.
The 5% limit applies the same way, but the formula uses a root-3 factor and phase-to-phase voltage (400 V in NZ) as the reference.
Mostly, yes. One exception: where the point of supply is the LV terminals of an on-site substation dedicated to the installation, the allowance rises to 7%. Stand-alone (off-grid) systems work under Clause 7.3 with a different budget.
NZ voltage drop calculator. AS/NZS 3000 Clause 3.6.2 flat 5% limit. Free, formula display, region-specific limits.